SEPARATING SENSIBLE-CAPACITY, GEOMETRY AND LATENT-STORAGE EFFECTS IN A MACRO-ENCAPSULATED RT52 RADIANT FLOOR: A COUNTERFACTUAL UNCERTAINTY FRAMEWORK

Authors

  • Kamolov Jurabek PhD in Technical Sciences, Assistant Professor, Department of Engineering Technologies and Renewable Energy Sources, Bukhara State University
  • Temirov Sokhib Assistant Professor, Department of Biomedical Engineering, Biophysics and Informatics, Bukhara State Medical Institute
  • Makhmudova Marjona Basic Doctoral Researcher, Department of Engineering Technologies and Renewable Energy Sources Bukhara State University

DOI:

https://doi.org/10.5281/zenodo.23525875

Abstract

Interpreting a temperature delay in a phase-change-material (PCM) radiant floor as latent heat is valid only when the PCM and reference specimens have comparable sensible thermal capacity and when hydraulic and measurement uncertainties are independently constrained. This paper develops a counterfactual uncertainty framework for a paired solar radiant-floor experiment in which the conventional slab is dctrl thick, whereas the PCM-integrated slab is dpcm thick and contains eleven steel macro-capsules filled with RT52. A geometry audit gives Vcone,ctrl of concrete in the control slab and Vconc,pcm of net concrete in the PCM slab after capsule displacement; the embedded PCM volume is Vpcm . Using the liquid-state density for molten filling gives a geometric RT52 upper-bound mass of mpcm, whereas the solid density would overestimate this inventory. Before latent heat is included, the PCM assembly has a sensible capacity of Csens, pcm versus Csens,ctrl for the control, an increase of about 30%. The incremental capacity of ΔCsens corresponds to ΔQsens over a ΔT = 15K excursion, which is already comparable with the nominal equal-flow excess charging energy of ΔQch,nom+ at f = 0.50. The embedded RT52 latent-capacity ceiling is approximately Qlat,max for hsf = 170 kJ/kg. Flow-split uncertainty changes the PCM-minus-control charging-energy difference from ΔQch+ 0.40 at f = 0.40 to ΔQch+ 0.60 at f = 0.60, with a zero crossing at fcrit. Sensor-offset analysis shows that sign-based surface-temperature findings are more robust than exact crossover time, persistence integral or latent-energy attribution. The experiment therefore supports a PCM-assembly thermal-load-shifting effect but does not uniquely identify a latent-energy fraction; geometry-matched controls, branch-specific flow measurement, direct PCM inventory determination and calibrated thermal boundaries are required for quantitative latent attribution.

Keywords

phase change material, RT52, radiant floor, sensible heat, latent heat, macroencapsulation, uncertainty, counterfactual validation, thermal storage

References

Rebelo, F., Brett, M., Figueiredo, A., Vicente, R., & Simões, N. (2026). Almeida RMSF, Ferreira VM. Experimental evaluation of a radiant floor system incorporating macroencapsulated phase change materials for improved heating and cooling performance. Energy. 2026;360:141692. https://doi.org/10.1016/j.energy.2026.141692. https://doi.org/10.1016/j.energy.2026.141692

Li, J., Xue, P., He, H., Ding, W., & Han, J. (2009). Preparation and application effects of a novel form-stable phase change material as the thermal storage layer of an electric floor heating system. Energy and Buildings, 41, 871–880.

Rebelo, F., Figueiredo, A., & Vicente, R. (2026). Almeida RMSF, Ferreira VM. Thermal performance of radiant floor systems incorporating phase change materials: effects of latent heat and phase change temperature range. Results in Engineering. 2026;32:112750. https://doi.org/10.1016/j.rineng.2026.112750. https://doi.org/10.1016/j.rineng.2026.112750

Rebelo, F., Figueiredo, A., & Vicente, R. (2024). Almeida RMSF, Ferreira VM. Experimental analysis of a radiant floor system incorporating phase change materials: Thermal performance and energy efficiency. Journal of Energy Storage. 2024;102:114084. https://doi.org/10.1016/j.est.2024.114084. https://doi.org/10.1016/j.est.2024.114084

Lin, K., Zhang, Y., Xu, X., Di, H., Yang, R., & Qin, P. (2005). Experimental study of under-floor electric heating system with shapestabilized PCM plates. Energy and Buildings, 37, 215–220. https://doi.org/10.1016/j.enbuild.2004.06.017

Sharshir, S. W., Joseph, A., Elsharkawy, M., Hamada, M. A., Kandeal, A. W., Elkadeem, M. R., et al. (2023). Thermal energy storage using phase change materials in building applications: A review of the recent development. Energy and Buildings. 2023;285:112908. https://doi.org/10.1016/j.enbuild.2023.112908. https://doi.org/10.1016/j.enbuild.2023.112908

Zhou, D., Zhao, C. Y., & Tian, Y. (2012). Review on thermal energy storage with phase change materials (PCMs) in building applications. Applied Energy, 92, 593–605. https://doi.org/10.1016/j.apenergy.2011.08.025

Cheng, W., Xie, B., Zhang, R., Xu, Z., & Xia, Y. (2015). Effect of thermal conductivities of shape stabilized PCM on under-floor heating system. Applied Energy, 144, 10–18. https://doi.org/10.1016/j.apenergy.2015.01.055

Ben Romdhane S, Amamou A, Ben Khalifa R, Mahjoub Saïd N, Younsi Z, Jemni A. A review on thermal energy storage using phase change materials in passive building applications. Journal of Building Engineering. 2020;32:101563.

Faraj, K., Khaled, M., Faraj, J., Hachem, F., & Castelain, C. (2021). A review on phase change materials for thermal energy storage in buildings: Heating and hybrid applications. Journal of Energy Storage. 2021;33:101913. https://doi.org/10.1016/j. est.2020.101913. https://doi.org/10.1016/j

Jin, X., Yang, J., Li, M., Huang, G., & Lai, A. C. K. (2022). Experimental and numerical study on the thermal energy storage performance of a novel phase-change material for radiant floor heating systems. Building and Environment. 2022;223:109491.

Chen, W., Liu, Y., Liang, X., Luo, F., Liao, T., Wang, S., Gao, X., Zhang, Z., & Fang, Y. (2023). Experimental and numerical investigations on radiant floor heating system integrated with macro-encapsulated phase change material. Energy. 2023;282:128375.

Li, G., Zhang, P., Xu, G., & Gantumur, T. (2024). Experimental study of advanced phase change materials to optimise the thermal storage performance of radiant floors: Towards a low-carbon energy system for grassland pastoral settlements. Construction and Building Materials. 2024;455:139220. https://doi.org/10.1016/j.conbuildmat.2024.139220. https://doi.org/10.1016/j.conbuildmat.2024.139220

Dolado, P., Mazo, J., Lázaro, A., Marín, J. M., & Zalba, B. (2012). Experimental validation of a theoretical model: Uncertainty propagation analysis to a PCM-air thermal energy storage unit. Energy and Buildings, 45, 124–131. https://doi.org/10.1016/j

Xia, Y., & Zhang, X. S. (2016). Experimental research on a double-layer radiant floor system with phase change material under heating mode. Applied Thermal Engineering, 96, 600–606. https://doi.org/10.1016/j.applthermaleng.2015.11.133

Rathore, P. K. S., & Shukla, S. K. (2019). Potential of macroencapsulated PCM for thermal energy storage in buildings: A comprehensive review. Construction and Building Materials, 225, 723–744. https://doi.org/10.1016/j.conbuildmat.2019.07.221

Lee, J., Wi, S., Yang, S., & Kim, S. (2020). Experimental study and assessment of high-tech thermal energy storing radiant floor heating system with latent heat storage materials. International Journal of Thermal Sciences. 2020;155:106410.

Zhou, G., & He, J. (2015). Thermal performance of a radiant floor heating system with different heat storage materials and heating pipes. Applied Energy, 138, 648–660. https://doi.org/10.1016/j.apenergy.2014.10.058

Karaağaç, M. O. (2025). Experimental investigation of a novel PCM-enhanced underfloor heating system for energyefficient sustainable buildings. Applied Thermal Engineering. 2025;275:126891. https://doi.org/10.1016/j. applthermaleng.2025.126891. https://doi.org/10.1016/j

Abass, P. J., & Muthulingam, S. (2024). Thermal energy storage performance of biaxial voided RCC roof slab integrated with macroencapsulated PCM for passive cooling of buildings. Journal of Energy Storage. 2024;88:111478. https://doi. org/10.1016/j.est.2024.111478.

Rathore, P. K. S., & Shukla, S. K. (2020). An experimental evaluation of thermal behavior of the building envelope using macroencapsulated PCM for energy savings. Renewable Energy, 149, 1300–1313. https://doi.org/10.1016/j

Shumuye, E. D., Fame, C. M., Mehrpay, S., Riaz, M. H., et al. (2026). A review on phase change material encapsulation and integration in building structures for thermal energy storage. Results in Engineering. 2026;30:110426. https://doi.org/10.1016/j. rineng.2026.110426. https://doi.org/10.1016/j

Prakash, J., Roan, D., Tauqir, W., Nazir, H., & Ali, M. (2019). Mada Kannan A. Off-grid solar thermal water heating system using phase-change materials: design, integration and real environment investigation. Applied Energy, 240, 73–83.

Qiao, X., Kong, X., & Fan, M. (2022). Phase change material applied in solar heating for buildings: A review. Journal of Energy Storage. 2022;55:105826. https://doi.org/10.1016/j.est.2022.105826. https://doi.org/10.1016/j.est.2022.105826

Wu, Y., Tang, Y., Li, Z., Ding, X., Yuan, W., Zhao, X., & Yu, B. (2016). Experimental investigation of a PCM-HP heat sink on its thermal performance and anti-thermal-shock capacity for high-power LEDs. Applied Thermal Engineering, 108, 192–203.

Khamraev, S., Kamolov, B., Tadjiboyev, S., Axmedova, B., Burieva, N., Ochilov, M., Samatova, S., & Sharopov, U. (2026). Experimental and theoretical analysis of thermo-hydraulic performance of a solar-collector-based hydronic floor heating system under climatic conditions of Uzbekistan. Energy. 2026;348:140399. https://doi.org/10.1016/j.energy.2026.140399. https://doi.org/10.1016/j.energy.2026.140399

Moffat, R. J. (1988). Describing the uncertainties in experimental results. Experimental Thermal and Fluid Science, 1(1), 3–17. https://doi.org/10.1016/0894-1777(88)90043-X

Coleman, H. W., & Steele, W. G. (2018). Experimentation, Validation, and Uncertainty Analysis for Engineers. 4th ed. Hoboken: Wiley; 2018. https://doi.org/10.1002/9781119417989. https://doi.org/10.1002/9781119417989

JCGM. Evaluation of measurement data – Guide to the expression of uncertainty in measurement. JCGM 100:2008(E). 2008. https://doi.org/10.59161/JCGM100-2008E

Courtois, E., Glouannec, P., Magueresse, A., & Loulou, T. (2022). Estimating thermal properties of phase change material from heat flux measurements. International Journal of Thermal Sciences. 2022;172:107307. https://doi.org/10.1016/j. ijthermalsci.2021.107307. https://doi.org/10.1016/j

Singh, B., Rai, R. S., Yadav, P., Srivastava, S., & Yadav, C. (2025). Application of phase change materials in solar water heating systems. https://doi.org/10.1016/j

Fazilati, M. A., & Alemrajabi, A. A. (2013). Phase change material for enhancing solar water heater, an experimental approach. Energy Conversion and Management, 71, 138–145. https://doi.org/10.1016/j.enconman.2013.03.034